| Typical core density | Approximately 80–150 kg/m³ | Approximately 30–40 kg/m³ | Approximately 35–45 kg/m³ | Approximately 15–25 kg/m³ | Approximately 35–60 kg/m³ |
| Declared thermal conductivity, λD | 0.034–0.041 W/m·K | 0.020–0.026 W/m·K | 0.021–0.028 W/m·K | 0.032–0.040 W/m·K | 0.018–0.023 W/m·K |
| Indicative core R-value at 100 mm | 2.44–2.94 m²·K/W | 3.85–5.00 m²·K/W | 3.57–4.76 m²·K/W | 2.50–3.13 m²·K/W | 4.35–5.56 m²·K/W |
| Indicative panel U-value at 100 mm | Approximately 0.32–0.40 W/m²·K | Approximately 0.20–0.26 W/m²·K | Approximately 0.21–0.28 W/m²·K | Approximately 0.30–0.39 W/m²·K | Approximately 0.18–0.23 W/m²·K |
| Thermal performance assessment | Good Requires greater thickness for the same R-value. | Very good High insulation value in relatively thin panels. | Very good Efficient insulation with good thickness-to-performance ratio. | Good Cost-effective insulation, generally thicker than PIR or phenolic foam. | Excellent Very low conductivity, but edge and joint detailing remain important. |
| Typical airborne sound insulation, Rw | Approximately 30–40 dB | Approximately 25–34 dB | Approximately 25–34 dB | Approximately 23–32 dB | Approximately 25–34 dB |
| Acoustic performance assessment | Best among listed cores Higher density and fibrous structure generally improve sound absorption and transmission loss. | Moderate to good Performance depends strongly on sheet thickness, joints, and panel mass. | Moderate to good Usually requires additional linings or resilient layers for demanding acoustic spaces. | Moderate Lightweight construction can limit airborne sound insulation. | Moderate to good May need a heavier lining system for high acoustic targets. |
| Typical reaction-to-fire classification | A1 or A2-s1,d0 for suitable non-combustible mineral wool systems | B-s1,d0 to B-s2,d0 for tested systems; formulation and facings are decisive | B-s2,d0 to C-s3,d0 for tested systems; formulation and facings are decisive | E to B-s2,d0 depending on density, flame-retardant treatment, and complete system | B-s1,d0 to B-s2,d0 for tested systems; product formulation is critical |
| Fire-resistance potential | Highest potential Suitable assemblies can achieve extended fire-resistance periods; joints and fixings must be tested. | Good when tested Fire resistance depends on panel thickness, joint design, facings, and tested assembly. | Good when tested Requires verified system data because combustible foam can affect fire development. | Limited to moderate Combustible core; use only where the complete tested system meets the required code level. | Good when tested Low flame spread is possible, but smoke and toxicity data must also be reviewed. |
| Moisture resistance | Generally resistant to liquid water when faced and detailed correctly; prolonged wetting can reduce thermal performance. | Low water absorption in closed-cell foam; damaged facings or unsealed joints can permit moisture ingress. | Low water absorption in closed-cell foam; protection from water and ultraviolet exposure is required. | Low water absorption in short-term exposure; prolonged wetting may increase moisture content and reduce insulation value. | Low water absorption, but open cuts, joints, and damaged facings must be sealed. |
| Water-vapour control | Usually vapour-permeable; a separate vapour-control layer may be needed in cold or humid assemblies. | Relatively vapour-resistant; joint continuity is essential to limit air and vapour leakage. | Relatively vapour-resistant; verify condensation risk at panel joints and penetrations. | Moderate vapour resistance; design the wall build-up to prevent interstitial condensation. | High vapour resistance; careful dew-point and drying-potential analysis is recommended. |
| Typical service-temperature considerations | Strong resistance to high temperatures; binder and facing limits still apply. | Protect from sustained temperatures that exceed the manufacturer’s tested service range; often around 100°C maximum for continuous exposure. | Protect from sustained high temperatures; continuous service limits are commonly around 100°C, subject to the system design. | Lower heat tolerance than mineral wool; avoid heat sources and high-temperature applications unless specifically tested. | Good thermal efficiency, but prolonged high-temperature exposure can cause shrinkage or degradation. |
| Best-fit applications | Fire-sensitive buildings, industrial enclosures, schools, hospitals, and projects requiring stronger acoustic performance. | Cold stores, warehouses, commercial buildings, and projects prioritizing high thermal efficiency at reduced thickness. | General industrial and agricultural buildings where thermal efficiency and cost balance are important. | Budget-sensitive buildings and moderate-risk applications where code requirements permit combustible insulation. | Space-constrained façades and high-performance envelopes requiring very low thermal conductivity. |
| Key selection checks for 2026 projects | Verify fire classification, fire-resistance test report, joint design, water repellency, and acoustic test results. | Verify reaction-to-fire classification, smoke rating, thickness-specific U-value, joint air-tightness, and condensation analysis. | Verify fire test evidence, dimensional stability, moisture protection, joint detailing, and long-term thermal design value. | Verify flame-retardant treatment, complete-system fire classification, water exposure limits, and local building-code acceptance. | Verify fire and smoke data, dimensional stability, vapour-control strategy, joint sealing, and service-temperature limits. |